4.13.3.3 Transistor Output Circuit
AH04HC-5A
Direct-current power supply
The output terminals of a transistor module are open-collector output terminals. If Y0.8 is a pulse train
output terminal of a transistor module, the output current passing through its output pull-up resistor must
be greater than 0.1 A to ensure that the transistor module operates normally.
A relay or a solenoid valve is used as a DC load. A diode is connected in parallel to absorb the surge
voltage which occurs when the load is OFF.
A bulb (incandescent lamp) is used as a DC load. A thermistor is connected in series to absorb the surge
current which occurs when the load is ON.
Y0.9 can not be connected to a power supply directly. It must be connected to a load.
LED
C h a p t e r 4 I n s t a l l i n g H a r d wa r e a n d W i r i n g
Load
Y0.8
< 0.5A
C0
Transistor output
Emergency stop
Fuse
4 - 1 0 3