The output terminals of a transistor module are open-collector output terminals. If Y0.8 is a pulse train
output terminal of a transistor module, the output current passing through its output pull-up resistor must
be greater than 0.1 A to ensure that the transistor module operates normally.
A relay or a solenoid valve is used as a DC load. A diode is connected in parallel to absorb the surge
voltage which occurs when the load is OFF.
A bulb (incandescent lamp) is used as a DC load. A thermistor is connected in series to absorb the
surge current which occurs when the load is ON.
Y0.9 can not be connected to a power supply directly. It must be connected to a load.
Mutually exclusive output: For example, Y0.10 controls the clockwise rotation of the motor, and Y0.11
controls the counterclockwise rotation of the motor. The interlock circuit which is formed, and the
program in the PLC ensure that there are protective measures if an abnormal condition occurs.
2.
Wiring diagrams for the differential output terminals
Wiring differential output terminals on AH05PM-5A/AH10PM-5A/AH15PM-5A, and an ASDA-
A/ASDA-A+/ASDA-A2 series AC servo drive
FP
RP
C h a p t e r 4 I n s t a l l i n g H a r d wa r e a n d W i r i n g
A C ser vo d ri ve
Y0 .0+
/P LS 43
Y0 .0-
PL S 41
FG0
Y0 .1+
/S IG N 36
Y0 .1-
SI GN 37
O pto cou p le r ci rcu i t
O pto cou p le r ci rcu i t
4 - 1 0 9