A H 5 0 0 H a r d w a r e a n d O p e r a t i o n M a n u a l
(3) Select a node number in the # cell for the data supply node. The node number in the # cell for the data
demanding node can not be the same as the node number in the # cell for the data supply node. After the
users select a node number, the PLC name corresponds to the node number will be appear in the Device
Name cell for the node number.
(4) Select a device type in the Register cell for the data supply node, and type an address in the Starting
Address cell for the data supply node. The device type selected in the Register cell for the data supply
node does not have to be the same as the device type selected in the Register cell for the data demanding
node.
(5) Type a data length in the Size cell. A word is a unit. The maximum data length is 1900 words. After the
users type a data length, the device ranges in the Range cells will change according to the data length
typed.
The users can create data exchange groups by following the steps described above. The device range in the
Range cell for a data demanding node can not overlap the device range in the Range cell for another data
demanding node whereas the device range in the Range cell for a data supply node can overlap the device
range in the Range cell for another data supply node. In other words, different demanders can ask for the same
data, but different data can not be store in the same block.
If the users want to delete a piece of data, they can click the piece of data, and click
11 - 4 0
.