Download Print this page

Delta AH500 Hardware Operation Manual page 95

Hide thumbs Also See for AH500:

Advertisement

A H 5 0 0 H a r d w a r e a n d O p e r a t i o n M a n u a l
Functional specifications
Analog-to-digital
conversion
Rated input range
Average function
Self-diagnosis
AH08PTG-5A
Electrical specifications
Number of analog
inputs
Applicable sensor
Supply voltage
Connector type
Overall accuracy
Conversion time
Isolation
Weight
Functional specifications
Analog-to-digital
conversion
Rated input range
Average function
Self-diagnosis
2 - 6 2
Centigrade (°C)
Pt100: -180°C~800°C
Ni100: -80°C~170°C
Pt1000: -180°C~800°C
Ni1000: -80°C~170°C
Range: 1~100
Disconnection detection
8
Three-wire configuration: Pt100/Ni100/Pt1000/Ni1000 sensor, and 0~300 Ω
Two-wire/Four-wire configuration: Pt100/Ni100/Pt1000/Ni1000 sensor, and
Pt100: DIN 43760-1980 JIS C1604-1989; 100 Ω 3850 PPM/°C
Pt1000: DIN EN60751; 1 kΩ 3850 PPM/°C
Ni100/Ni1000: DIN 43760
24 VDC (20.4 VDC~28.8 VDC) (-15%~+20%)
Removable terminal block
The error is ±1°C of a Pt100/Pt1000/Ni100/Ni1000 sensor's temperature.
The error is ±0.1% of a resistance in the range of 0 Ω to 300 Ω.
Quick mode:
Four-wire/Two-wire configuration: 20 ms/channel
Three-wire configuration: 200 ms/channel
General mode: A conversion time will be gotten after the conversion time of
the two channels in a group is added up.
Four-wire/Two-wire configuration: 200 ms/channel
Three-wire configuration: 400 ms/channel
An analog circuit is isolated from a digital circuit by a digital integrated circuit,
and the analog channels are isolated from one another by optocouplers.
Isolation between a digital circuit and a ground: 500 VDC
Isolation between an analog circuit and a ground: 500 VDC
Isolation between an analog circuit and a digital circuit: 500 VDC
Isolation between two group circuits: 500 VDC
Isolation between the 24 VDC and a ground: 500 VDC
255g
Centigrade (°C)
Pt100: -180°C~800°C
Ni100: -80°C~170°C
Pt1000: -180°C~800°C
Ni1000: -80°C~170°C
Range: 1~100
Disconnection detection
Fahrenheit (°F)
Pt100: -292°F~1,472°F
Ni100: -112°F~338°F
Pt1000: -292°F~1,472°F
Ni1000: -112°F~338°F
input impedance
0~300 Ω input impedance
Fahrenheit (°F)
Pt100: -292°F~1,472°F
Ni100: -112°F~338°F
Pt1000: -292°F~1,472°F
Ni1000: -112°F~338°F
Input impedance
0~300 Ω
Input impedance
0~300 Ω

Advertisement