A H 5 0 0 H a r d w a r e a n d O p e r a t i o n M a n u a l
2.
Definitions of the pins in the PROFIBUS-DP port
PIN
1
2
3
4
5
6
7
8
9
3.
Setting a PROFIBUS node address by means of the address knobs
The address knobs of AHRTU-PFBS-5A are used for setting the node address of AHRTU-PFBS-5A
on a PROFIBUS-DP network. There are two address knobs. They are a knob corresponding to x16
and a knob corresponding to x16
The range for setting the node address is described below.
Address
H'1~H'7D
H'0 or H'7E~H'FF
Example: If users need to set the node address of AHRTU-PFBS-5A to 26 (decimal value), they have
to turn the knob corresponding to x16
26 (decimal value)=1A (hexadecimal value)=1x16
Points for attention:
If users set the node address of AHRTU-PFBS-5A when AHRTU-PFBS-5A is not supplied with
power, they have to power AHRTU-PFBS-5A after the node address of AHRTU-PFBS-5A is set.
If users change the node address of AHRTU-PFBS-5A when AHRTU-PFBS-5A is powered, the
change will not take effect immediately after the node address of AHRTU-PFBS-5A is changed,
and it will take effect after the users cut off the power supplied to AHRTU-PFBS-5A and then
power AHRTU-PFBS-5A again.
To prevent the address knobs on AHRTU-PFBS-5A from being scratched, please carefully use a
slotted screwdriver to rotate the address knobs on AHRTU-PFBS-5A.
2 - 11 2
PIN name
--
--
RxD/TxD-P
Receiving/Sending data (P (B))
--
DGND
Data reference potential (C)
VP
Supply positive voltage
--
RxD/TxD-N
Receiving/Sending data (N (A))
--
1
. The range for one address knob is 0~F.
Definition
Valid PROFIBUS address
Invalid PROFIBUS address
Description
N/C
N/C
N/C
N/C
N/C
1
to "1" and the knob corresponding to x16
1
0
+Ax16
.
9
5
6
1
0
,
1
x16
0
x16
0
to "A".