If the length of data received is larger than the length set, the first 20-word data will be stored in D100~D119,
and the data after the first 20-word data will be discarded. Likewise, if the length of data received is less than
the length set, the data will be stored in the devices starting from D100, and the values in devices where no new
data is stored will be retained.
If no data is transmitted, and 60 seconds have elapsed, the CPU module will close the socket, and terminate
the connection.
8.1.3.10 Ethernet – Advance: Web
Select the Enable Web Function checkbox to enable the built-in web monitoring function of the CPU module.
Enter the IP address of the CPU module on the search bar. After the parameter is downloaded to the CPU
module correctly, users can view the parameters, including I/O, devices, system log, and network
configurations of the CPU module through a web browser. Refer to section 11.4 for more information.
The web page function is only available for AH5x0-EN Series (FW V1.08 or later) and AH5x1-EN (FW V2.03
or later).