12.3.2 Troubleshooting for AH02HC-5A/AH04HC-5A

Error
Description
code
The linear accumulation in
16#A001
channel 0 exceeds the range.
The scale set for channel 0
16#A002
exceeds the range.
The number of cycles set for
16#A003
channel 0 exceeds the range.
The comparison value set for
16#A004
channel 0 exceeds the range.
A limit value set for channel 0 is
16#A005
incorrect.
The interrupt number set for
16#A006
channel 0 exceeds the range.
The linear accumulation in
16#A011
channel 1 exceeds the range.
The scale set for channel 1
16#A012
exceeds the range.
The number of cycles set for
16#A013
channel 1 exceeds the range.
The comparison value set for
16#A014
channel 1 exceeds the range.
A limit value set for channel 1 is
16#A015
incorrect.
The interrupt number set for
16#A016
channel 1 exceeds the range.
The linear accumulation in
16#A021
channel 2 exceeds the range.
The scale set for channel 2
16#A022
exceeds the range.
The number of cycles set for
16#A023
channel 2 exceeds the range.
The comparison value set for
16#A024
channel 2 exceeds the range.
A limit value set for channel 2 is
16#A025
incorrect.
The interrupt number set for
16#A026
channel 2 exceeds the range.
1 2 - 4 8
Remedy
To clear the linear accumulation, users need to set bit 1 in
CR0 to ON by means of FROM/TO.
Check the module parameter in HWCONFIG.
The scale set for channel 0 should be in the range of 0 to
32767.
Check the module parameter in HWCONFIG.
The number of cycles set for channel 0 should be in the
range of 2 to 60.
Check the module parameter in HWCONFIG.
The comparison value set for channel 0 should be in the
range of -999999999 to 999999999.
Check the module parameter in HWCONFIG.
A limit value of set for channel 0 should be in the range of
-200000 to 200000.
Check the module parameter in HWCONFIG.
The interrupt number set for channel 0 should be in the
range of 0 to 31.
To clear the linear accumulation, users need to set bit 1 in
CR28 to ON by means of FROM/TO.
Check the module parameter in HWCONFIG.
The scale set for channel 1 should be in the range of 0 to
32767.
Check the module parameter in HWCONFIG.
The number of cycles set for channel 1 should be in the
range of 2 to 60.
Check the module parameter in HWCONFIG.
The comparison value set for channel 1 should be in the
range of -999999999 to 999999999.
Check the module parameter in HWCONFIG.
A limit value of set for channel 1 should be in the range of
-200000 to 200000.
Check the module parameter in HWCONFIG.
The interrupt number set for channel 1 should be in the
range of 0 to 31.
To clear the linear accumulation, users need to set bit 1 in
CR56 to ON by means of FROM/TO.
Check the module parameter in HWCONFIG.
The scale set for channel 2 should be in the range of 0 to
32767.
Check the module parameter in HWCONFIG.
The number of cycles set for channel 2 should be in the
range of 2 to 60.
Check the module parameter in HWCONFIG.
The comparison value set for channel 2 should be in the
range of -999999999 to 999999999.
Check the module parameter in HWCONFIG.
A limit value of set for channel 2 should be in the range of
-200000 to 200000.
Check the module parameter in HWCONFIG.
The interrupt number set for channel 2 should be in the