(4) After the users make sure that the summary in the CARD Utility window is consistent with the data
restoration which will be performed, they can click Execute.
If the users click Cancel in the process of restoring data to the AH500 series CPU module, the data will
not be completely restored. To prevent the AH500 series CPU module from operating incorrectly, the
users have to restore the AH500 series CPU module to the factory setting if they do not perform the data
restoration again. Besides, the AH500 series CPU module will still performs the data restoration even if
the users click Cancel in the process of restoring a backup file in the memory card inserted in the AH500
series CPU module. The users can turn off the AH500 series CPU module to stop the data restoration
from being performed.
If restoration source/restoration destination contains a password and an ID, the password and the ID will
be processed.
Data restoration
Memory cardCPU module
ComputerCPU module
Computer ISPSoft project
(5) After the data restoration is performed, the users can click Home or Close in the CARD Utility window.
a. The ID in the backup file must be the same as the ID in the CPU
module, otherwise the data restoration will not be performed.
b. If there is a PLC password in the CPU module, the password in
the backup file must be the same as the PLC password in the
CPU module. Otherwise the data restoration will not be
performed.
c. If there is no PLC password in the CPU module, and there is a
password in the backup file, the system will perform the data
restoration, and the password in the backup file will become the
PLC password in the CPU.
a. The ID in the backup file must be the same as the ID in the CPU
module, otherwise the data restoration will not be performed.
b. If there is a PLC password in the CPU module, the password in
the backup file must be the same as the PLC password in the
CPU module. Otherwise the data restoration will not be
performed, and a message will appear.
c. If there is no PLC password in the CPU module, and there is a
password in the backup file, the system will perform the data
restoration, and the password in the backup file will become the
PLC password in the CPU.
Before restoring, the PLC password is required, if there is a PLC
password in the backup file. After restoring is done, the Project
password, and the program ID will be restored in the ISPSoft
Project. As for the PLC password and the PLC ID, they cannot be
saved in the ISPSoft project.
C h a p t e r 7 Me m o r y C a r d
Description
7 - 1 7