Messages and fault codes

8.1

Fault codes

The inverter has the capability to identify internal and external fault conditions, the most
common faults are shown in the following tables. More detailed information on faults can be
found in the Parameter List.
Table 8- 1
Fault Number Meaning
F00001
F00002
F00003
F00004
F00030
F00041
F00062
F00070
F00071
F00073
SINAMICS G110D
Operating Instructions, 07/2016, FW V3.63, A5E36768472B AB
Fault codes description
Cause
Overcurrent - Motor power does not correspond to the inverter power
Remedy
Check that the motor and inverter power ratings are the same.
Cause
Overvoltage - mains supply voltage too high or motor is in regenerative
mode.
Remedy
Check the mains supply voltage
Cause
Undervoltage - mains / 24 V supply has failed
Remedy
Check mains supply / 24 V supply
Cause
Inverter over temperature - the inverter has exceeded the temperature
limits
Remedy
Check motor loading, pulse frequency setting, ambient temperature or if
fitted the fan is working correctly.
Cause
Fan failure
Remedy
Fain no longer working - replace fan.
Cause
Motor data identification failure
Remedy
check that the motor is connected to the inverter correctly and that the
motor data entered is correct.
Cause
SD card contents invalid
Remedy
Recopy data to SD card and ensure that the process is completed.
Cause
PLC setpoint fault - the communications failure monitoring times, set by
P2040 has expired.
Remedy
Check:
If the AS-interface master has stopped or is in 'program' mode.
The cable connection between the bus nodes.
check if the communication monitoring time has been set too short in
P2040.
Cause
USS setpoint fault - no setpoint values from USS during telegram off time.
Remedy
Check and improve monitoring timing using STARTER
Cause
Control Panel setpont fault - no setpoint values from Control Panel during
telegram off time.
Remedy
Check and improve - if necessary - the value in P3984
Acknowledge fault
If fault persists, contact Service Department or change Inverter.