Incremental Encoder Interface Modules; Table 110: Ssi Transmitter Interface Modules - WAGO -I/O-IPC-C6 Manual

Wago-i/o-system 750
Hide thumbs Also See for WAGO-I/O-IPC-C6:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
758-874/000-131 WAGO-I/O-IPC-C6
The above SSI Transmitter Interface modules have a total of 4 bytes of user data
in the Input Process Image, which has 2 words mapped into the image.
Word alignment is applied.

Table 110: SSI Transmitter Interface Modules

Input Process Image
Offset
0
1
18.2.5.7

Incremental Encoder Interface Modules

750-631/000-004, -010, -011
The above Incremental Encoder Interface modules have 5 bytes of input data and
3 bytes of output data. The following tables illustrate the Input and Output Process
Image, which have 4 words into each image. Word alignment is applied.
Table 111: Incremental Encoder Interface Modules 750-631/000-004, --010, -011
Input Process Image
Offset
0
1
2
3
Output Process Image
Offset
0
1
2
3
750-634
The above Incremental Encoder Interface module has 5 bytes of input data (6
bytes in cycle duration measurement mode) and 3 bytes of output data. The
following tables illustrate the Input and Output Process Image, which has 4 words
mapped into each image. Word alignment is applied.
Manual
Version 1.0.0
Byte Destination
High Byte
D1
D3
Byte Destination
High Byte
-
D1
-
D4
Byte Destination
High Byte
-
D1
-
-
Low Byte
D0
D2
Low Byte
S
not used
D0
-
D3
Low Byte
C
not used
D0
-
-
I/O Modules
241
Description
Data bytes
Description
Status byte
Counter word
not used
Latch word
Description
Control byte
Counter setting word
not used
not used

Advertisement

Table of Contents
loading

This manual is also suitable for:

I/o-system 750758-874/000-111

Table of Contents