Register Services; Table 45: Reading Analog Input Terminals Using Fc3, Fc4, Fc23; Table 46: Writing Of Analog Output Terminals Using Fc6, Fc16, Fc23 - WAGO -I/O-IPC-C6 Manual

Wago-i/o-system 750
Hide thumbs Also See for WAGO-I/O-IPC-C6:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
758-874/000-131 WAGO-I/O-IPC-C6
10.2.1

Register Services

With the register services, determine or change the statuses of analog input and
output terminals for the following address ranges:

Table 45: Reading Analog Input Terminals Using FC3, FC4, FC23

MODBUS Address
0x0000 – 0x00FF
(0 – 255)
0x100 – 0x1FF
(256 – 511)
0x1000 – 0x2FFF
(4096 – 12287)
0x3000 – 0x3FFF
(12288 – 16384)
or can be set to a
maximum of
0xFFFF (65534)

Table 46: Writing of Analog Output Terminals Using FC6, FC16, FC23

MODBUS Address
0x0000 – 0x00FF
(0 – 255)
0x100 – 0x1FF
(256 – 511)
0x1000 – 0x2FFF
(4096 – 12287)
0x3000 – 0x3FFF
(12288 – 16384)
or can be set to a
maximum of
0xFFFF (65534)
Manual
Version 1.0.0
Addresses in CoDeSys
%IW0 ... %IW255
%QW256 ... %QW511
See MODBUS
configuration register
%MW0 ... %MW4095
%MW0 ... %MW53247
Addresses in CoDeSys
%QW0 ... %QW255
%IW256 ... %IW511
See MODBUS
configuration register
%MW0 ... %MW4095
%MW0 ... %MW53247
MODBUS/TCP
Description
Reading analog or digital input values.
Physical address space of 256 words for
the input data.
Read the PFC variables
MODBUS Configuration Register
Retain memory (8 kB)
Non-volatile PLC variables
Retain memory (24 kB)
Non-volatile PLC variables
Description
Writing analog or digital output values.
Physical address space of 256 words for
the output data.
Write the PFC variables
MODBUS Configuration Register
Retain memory (8 kB)
Non-volatile PLC variables
Retain memory (24 kB)
Non-volatile PLC variables
93

Advertisement

Table of Contents
loading

This manual is also suitable for:

I/o-system 750758-874/000-111

Table of Contents