200
Diagnostics
Pos: 51.5 /Serie 758 (Funk, IPC und PFC)/Diagnose/Diagnose LED-Signalisierung 758-87x Tabelle 1_1 DPM @ 10\mod_1312535342005_21.doc @ 76011 @ @ 1
Table 72: I/O-IPC Operational Messages
Position LED
41
42
Pos: 51.6 /Dokumentation allgemein/Gliederungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.doc @ 21810 @ @ 1
Color/Status
RDY
Yellow
Green flashing
(irregular)
RUN
Green
Green flashing
(5 Hz)
Green flashing
(irregular)
WAGO-I/O-SYSTEM 750
758-874/000-131 WAGO-I/O-IPC-C6
Cause
Explanation/Remedy
I/O-IPC is ready for
-
operation.
There is a system
Restart the I/O-IPC. If
error in the
this malfunction
PROFIBUS
recurs, contact
controller.
WAGO support.
The I/O-IPC has
established at least
one connection to a
configured
PROFIBUS slave.
You have stopped
communication with
the slave (ERR LED
also lights up).
The I/O-IPC cannot
Check the cables to
communicate with the
the slaves and check
slaves.
these for
malfunctions.
There is a missing or
Check the CoDeSys
defective
configuration.
configuration of the
PROFIBUS or a time
error of the host
watchdog has
occurred.
-
-
Manual
Version 1.0.0