Table 75: Meaning of Blink Codes and Measures to Eliminate Errors
Error Argument Cause
3
4
5
6
7
8
9
10
11
12
14
Error Code 2: Not Used
-
Manual
Version 1.0.0
Unknown module type of
the flash program memory
Error occurred while writing
to the flash memory
Error occurred while erasing
a flash sector
The I/O module
configuration after an
internal bus reset differs
from the one after the last
I/O-IPC start-up.
Error occurred while writing
to the serial EEPROM
Invalid hardware/firmware
combination
Invalid checksum in the
serial EEPROM
Fault when initializing the
serial EEPROM.
Error occurred while
reading from the serial
EEPROM
Time to access the serial
EEPROM exceeded
Maximum number of
gateway or mailbox
modules exceeded.
-
Correction
- Switch the supply voltage of the
I/O-IPC off and change it.
- Then switch the supply voltage on again.
- Switch the supply voltage of the
I/O-IPC off and exchange it.
- Then switch the supply voltage on again.
Restart the I/O-IPC by
- switching the supply voltage off and
then on again, or
- press the reset button on the I/O-IPC.
- Switch the supply voltage of the
I/O-IPC off and exchange it.
- Then switch the supply voltage on again.
- Switch the supply voltage of the
I/O-IPC off and reduce the number of
I/O modules.
- Then switch the supply voltage on again.
- Switch the supply voltage of the
I/O-IPC off and exchange it.
- Then switch the supply voltage on again.
- Switch the supply voltage of the
I/O-IPC off.
- Reduce the number of gateway or
mailbox modules.
- Then switch the supply voltage on again.
-
Diagnostics