18.2.5.15 Vibration Velocity/Bearing Condition Monitoring VIB I/O

750-645
The Vibration Velocity/Bearing Condition Monitoring VIB I/O has a total of 12
bytes of user data in both the Input and Output Process Image (8 bytes of module
data and 4 bytes of control/status). The following table illustrates the Input and
Output Process Image, which have 8 words mapped into each image.
Word alignment is applied.

Table 122: Vibration Velocity/Bearing Condition Monitoring VIB I/O 750-645

Input and Output Process Image
Offset
0
1
2
3
4
5
6
7
Pos: 60.17 /Serie 750 (WAGO-I/O-SYSTEM)/Prozessabbild Mapping/ETHERNET - EtherNet/IP - MODBUS/TCP/PA ETHERNET - 753-646 KNX/EIB (750-830, -842, -849) @ 5\mod_1253540550198_21.doc @ 41890 @ 4 @ 1

18.2.5.16 KNX/EIB/TP1 Module

753-646
The KNX/TP1 module appears in router and device mode with a total of 24-byte
user data within the input and output area of the process image, 20 data bytes and
2 control/status bytes. Even though the additional bytes S1 or C1 are transferred
as data bytes, they are used as extended status and control bytes. The opcode is
used for the read/write command of data and the triggering of specific functions
of the KNX/EIB/TP1 module. Word-alignment is used to assign 12 words in the
process image. Access to the process image is not possible in router mode.
Telegrams can only be tunneled.
In device mode, access to the KNX data can only be performed via special
function blocks of the IEC application. Configuration using the ETS engineering
tool software is required for KNX.
Byte Destination
High Byte
-
D1
-
D3
-
D5
-
D7
758-874/000-131 WAGO-I/O-IPC-C6
Low Byte
C0/S0
not used
D0
(log. Channel 1, Sensor input 1)
C1/S1
not used
D2
(log. Channel 2, Sensor input 2)
C2/S2
not used
D4
(log. Channel 3, Sensor input 3)
C3/S3
not used
D6
(log. Channel 4, Sensor input 2)
WAGO-I/O-SYSTEM 750
Description
Control/status byte
(log. Channel 1,
Sensor input 1)
Data bytes
Control/status byte
(log. Channel 2,
Sensor input 2)
Data bytes
Control/status byte
(log. Channel 3,
Sensor input 1)
Data bytes
Control/status byte
(log. Channel 4,
Sensor input 2)
Data bytes
Manual