WAGO-I/O-SYSTEM 750
758-874/000-131 WAGO-I/O-IPC-C6
19.1.1
Calls for the "WAGOConfigToolLIB.lib" Library
The following table shows calls that allow you to configure and parameterize the
I/O-IPC from the PLC program or Linux via the "ConfigTool" function block. In
addition to WBM and the "IPC Configuration Tool", this is another variant to
configure the I/O-IPC for operational requirements.
The configuration directory under Linux is:
0001
get_coupler_details processor-type
Figure 119: Graphical representation of the "ConfigTool" function block
Table 130: Description of the configuration scripts for "Information"
Parameter
Information
Coupler Details: Identified various information of the I/O-IPC
Order Number
Processor Type
Fieldbus Type
Firmware
Revision
Licence
Information
Kbus FW
Revision
CoDeSys
Webserver
Version
Network Details Eth0: Identifies the parameters of the ETHERNET interfaces currently
used
State
Mac Address
IP Address
Subnet Mask
Network Details Eth1
"
See
Network Details Eth1
Manual
Version 1.0.0
xStart
bEnable
stCallString
Status Call
get_coupler_details
read
order-number
get_coupler_details
read
processor-type
get_coupler_details
read
fieldbus-type
get_coupler_details
read
firmware-revision
get_coupler_details
read
license-information
get_coupler_details
read
kbus-fw-revision
get_coupler_details
read
codesys-webserver-
version
get_actual_eth_config
read
eth0 state
get_actual_eth_config
read
eth0 mac-address
get_actual_eth_config
read
eth0 ip-address
get_actual_eth_config
read
eth0 subnet-mask
"
. When calling, replace eth0 with eth1
/etc/config-tools/
Configtool_FB
configToolFB
bDone
bBusy
stResultString
iFbResult
iConfigToolResult
stConfigToolErrorString
Output/Input
Item number of the
I/O-IPC.
Processor type of the
I/O-IPC
Fielbus type of the I/O-IPC
Firmware version of the
I/O-IPC
CoDeSys license
information
Firmware version of the
I/O module controller
CoDeSys Webserver
version
Status of the interface:
enabled
disabled
Display of the MAC
address
Display of the current
IP address
Display of the current
subnet mask
Appendix
255
Done
bBusy
sResult='Intel(R) Pentium(R) M
Status=0
ConfigToolStatus=0
sConfigToolErrorString="
Validity
immediate
immediate