202
Diagnostics
Pos: 51.9 /Serie 758 (Funk, IPC und PFC)/Diagnose/Diagnose LED-Signalisierung 758-87x ERR- und STA-LED DPM @ 10\mod_1313148785346_21.doc @ 76693 @ @ 1
Table 74: Operating reports of ERR and STA LED
ERR (39)
Color/Status
Off
Off
Red
Red
Off
Pos: 51.10 /Dokumentation allgemein/Gliederungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.doc @ 21810 @ @ 1
STA (40)
Explanation/Remedy
Color/Status
Off
PROFIBUS master is not configured or has
not received the token from the PROFIBUS
network.
Green
PROFIBUS master holds the token and is
ready to send telegrams
Off
PROFIBUS master has a short circuit.
Green
Communication problem between the
PROFIBUS master and at least one
PROFIBUS-DP slave.
Green flashing
PROFIBUS master exchanges the token with
(irregular)
another master in the PROFIBUS network.
WAGO-I/O-SYSTEM 750
758-874/000-131 WAGO-I/O-IPC-C6
Manual
Version 1.0.0