Figure 91: Online view of the arrays EXTENDEDINFO in binary representation 2

Channel 1 of the 750-466 Input Module
Array Element
30
Array Element
31
32
33 – 35
Channel 2 of the 750-466 Input Module
Array Element
33 – 35
Array Element 129
The number of projected slaves is specified in the array element 129.
Pos: 46.17 /Dokumentation allgemein/Gliederungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.doc @ 21810 @ @ 1
Manual
Version 1.0.0
PROFIBUS Master in CoDeSys 2.3
Diagnostics of the 1st channel,
3 bytes
Diagostics of the 2nd channel,
3 bytes
Content
10000100
Content
01000000
10101000
Channel 2
Content
See channel 1
Meaning
Slot for the input module. In
this case, the third (slot 4).
Note:
Fieldbus coupler and
controller, including the power
supply module, reserve the 1st
slot. Therefore the first I/O
module is inserted in the second
slot.
Meaning
The first two bits indicate the
type of channel:
01 Input channel
10 Output channel
11 Input and output channel
The other bits indicate the
channel number.
The first three bits indicate the
type of channel:
000 No assignment
001 1 bit
010 2 bit
100 1 byte
101 1 word
110 2 words
The other bits indicate I/O
module errors.
Meaning
165