WAGO-I/O-SYSTEM 750
758-874/000-131 WAGO-I/O-IPC-C6
Pos: 34.11 /Serie 758 (Funk, IPC und PFC)/Beschreibung der Schnittstellen/Beschreibung der Schnittstellen 758-87x (onBoard I/Os, USB, ...) Ende @ 10\mod_1314943172178_21.doc @ 78022 @ 222 @ 1
Digital Inputs
The two digital inputs are independent of the internal data bus. This means that
digital signals are processed even if the internal data bus breaks down.
Voltage range
Max. current per
channel
Channels
Input impedance
Characteristics
Figure 8: Connection of integrated inputs
Manual
Version 1.0.0
Description of I/O-IPC Interfaces
Low: -3 V ... +5 V
High: +11 V ... +30 V (+24 V standard)
5 mA
2
Min. 1.5 kOhm
Max. 6 kOhm at 30 V
Optocoupler, 2 kV
Low-pass filter, 10 kHz
Current limitation
Surge protection
Reverse voltage protection
I/O-IPC
1
2
9
10
37