PROFIBUS Master in CoDeSys 2.3
DP Parameters
Figure 65: "DP Parameters" tab
The following table explains the parameters listed in the register:
Table 59: Description of the Parameters
DP Parameters
Info
Addresses
Station address
Highest station address
Mode
Auto Clear Mode
Automatic startup
GSD file ...
Groups ...
758-874/000-131 WAGO-I/O-IPC-C6
General information on the PROFIBUS master from the GSD
file.
Address of the I/O-IPC in a PROFIBUS network.
Highest station address in the PROFIBUS network. This value is
automatically set.
When errors are detected on the fieldbus, the I/O-IPC initiates
the OPERATE state and switches the outputs to the
"FAILSAFE" state. Connected slaves that support the DPV-1
protocol are also put in this state.
When errors are detected on the bus, the master goes into the
Clear state and sends data telegrams of zero length to the slaves.
A reset is required to exit this state.