88
Configuration
Table 40: Description of the parameters for the "SNMP" page
SNMP v3 Configuration
A list of all configured v3 users is indicated here. The number of users is in principle not limited
by the I/O-IPC. You have the opportunity to delete individually configured Users via [DELETE].
At the end of the list, you will find a form for compiling a completely new User. Individual
configuration data of already existing Users cannot be changed.
Security Authentication Name
Authentication Type
Authentication Key
(min. 8 char.)
Privacy
Privacy Key
(min. 8 char.)
Notification Receiver IP
9.1.17

I/O Configuration

On this page, the I/O module configuration connected to the I/O-IPC is shown
with the process values of the individual I/O modules.

Table 41: Description of the parameters on the "I/O Configuration" page

I/O configuration and vales
Pos
Module
Type
Channel
Values
User Name. This must be unique; an already present User name
is not accepted by the new entry.
The community name can be up to 32 characters long and may
not include spaces.
Authentication type for SNMP v3 packages. Possible values are:
- Use no authentication ("None")
- Message Digest 5 ("MD5")
- Secure Hash Algorithm ("SHA")
Key string for authentication.
The authentication key must be min. 8 characters and max. 32
characters without blank characters.
Encryption algorithm for SNMP Messages. Possible values are:
- No encryption ("None")
- Data Encryption Standard ("DES")
- Advanced Encryption Standard ("AES")
Key string for encryption ("privacy") of the SNMP message. If
nothing is entered here, the "Authentication Key" is
automatically used.
The Privacy Key must be min. 8 characters and max. 32
characters without blank characters.
IP address for a Trap Receiver for v3 Traps. In case no v3 Traps
should be sent for this user, the field remains empty.
Position of the I/O module connected to the I/O-IPC. Passive I/O
modules do not appear in WBM (e.g. 750-600, -602, ...).
Product number of the I/O module or abbreviation.
Description of which is the I/O module in question (8DI, 4AO, etc.).
Specification of the module position and channel number of the I/O
module.
Display of the process data at the time of the last update of the "I/O
Configuration" page. To display the current process data, update the
page.