50

Connecting the Supply Voltage

Pos: 38.1 /Serie 758 (Funk, IPC und PFC)/Anschluss Daten- und Versorgungskabel/Anschluss Daten- und Versorgungskabel 758-87x Einleitung @ 10\mod_1312441245283_21.doc @ 75864 @ 1 @ 1
7
Connecting the Supply Voltage
The supply voltage is connected as follows, depending on the application area of
the I/O-IPC:
Scope of Delivery
The 750-602 Supply Module is no longer included in the scope of delivery as of
HW Version 11.

Table 19: Use of 750-602/626 depending on the application area of the I/O-IPC

Application Area
Cable length < 3 m
Pos: 38.2 /Serie 758 (Funk, IPC und PFC)/Anschluss Daten- und Versorgungskabel/Anschluss Daten- und Versorgungskabel 758-87x Leitungslänge > 3 m @ 10\mod_1313496549855_21.doc @ 77084 @ @ 1
Cable length > 3 m
Pos: 38.3 /Serie 758 (Funk, IPC und PFC)/Anschluss Daten- und Versorgungskabel/Anschluss Daten- und Versorgungskabel 758-87x Einleitungsende @ 10\mod_1313496553308_21.doc @ 77088 @ 222 @ 1
7.1

Notes

Electric voltage!
Only operate the I/O-IPC with 24 V DC PELV (Protective Extra Low Voltage) or
SELV (Safety Extra Low Voltage) power sources. There is a danger of electric
shock if this precaution is not observed.
Interruption of the supply voltage
If the power supply is interrupted by more than 1ms, the I/O-IPC is backed up and
automatically restarted.
To ensure electrical isolation, a power supply unit each for the electronic
supply and the field supply must be used.
Connect the power supply lines only when they are in a de-energized state.
Keep power supply lines a sufficient distance away from electromagnetic
sources of interference in order to maintain a high level of interference
resistance of the 750 Series components against electromagnetic emissions.
When laying any lines, make sure that you do not lay them within the shear
range of movable machine parts.
Observe the correct layout of the potential equalization.
758-874/000-131 WAGO-I/O-IPC-C6
Filter Modules
750-602
750-626
WAGO-I/O-SYSTEM 750
Power Supply
See section, "Power Supply via
750-602 Supply Module"
See section "Power Supply via
750-626 Filter Module"