2ai 4-20ma hart ex i 2-channel analog input; hart; intrinsically safe, 2ai 4-20ma hart ne43 ex i 2-channel analog input; hart; namur ne43; intrinsically safe (100 pages)
WAGO Kontakttechnik GmbH & Co. KG declines all liability resulting from improper action and damage to WAGO products and third party products due to non-observance of the information contained in this manual.
Routines or advice for efficient use of the device and software optimization. More information References on additional literature, manuals, data sheets and INTERNET pages 1.3 Number Notation Number Code Example Note Decimal normal notation Hexadecimal 0x64 C notation Binary '100' Within ', '0110.0100' Nibble separated with dots WAGO-I/O-SYSTEM 750 I/O Modules...
1.5 Scope This manual describes the Analog Output Module 750-560 2 AO 0-10V DC 10Bit 10mA 24V of the modular WAGO-I/O-SYSTEM 750. Handling, assembly and start-up are described in the manual of the Fieldbus Coupler. Therefore this documentation is valid only in the connection with the appropriate manual.
2.1.1.2 Description The analog output module 750-560 creates a standardized signal of 0-10 V. The module has two short circuit protected output channels and enables, for example, the direct wiring of two 3-conductor actuators to the connections AO 1, AC/DC 24 V and 0 V or AO 2, AC/DC 24 V and 0 V. The signals are transmitted via AO 1 and AO 2.
However, if such a case should occur, another supply module must be added. The analog output module 750-560 can be used with all couplers/controllers of the WAGO-I/O-SYSTEM 750 (except for the economy types 750-320, - 323, -324 and -327).
Approvals (cf. Chapter 2.2 of the Coupler/Controller Manual) Conformity Marking More Information Detailed references to the approvals are listed in the document "Overview Approvals WAGO-I/O-SYSTEM 750", which You can find on the CD ROM ELECTRONICC Tools and Docs (Item-No.: 0888-0412-0001-0101) or in the Internet under: www.wago.com ->...
Process Image 2.1.1.6 Process Image The analog output module 750-560 transmits 16-bit data and 8 status bits per channel. The digitalized output value is transmitted in a data word (16 bits) as output byte 0 (low) and output byte 1 (high) via the process image of the coupler / controller.