Installing and Removing the I/O-IPC
Pos: 36.14 /Serie 758 (Funk, IPC und PFC)/Montieren/Montage 758-87x allgemein 3 @ 10\mod_1312439346890_21.doc @ 75843 @ 2 @ 1
6.5

Connecting the I/O Module to the I/O-IPC

After mounting the I/O-IPC on a mounting rail, connect the I/O modules required
for your application to the I/O-IPC. You can connect up to 64 750/753 Series
I/O Modules to the I/O-IPC. The number is dependent on the total length of the
connected I/O modules. This may amount to a maximum of 780 mm, including
the end module, and the maximum size of the process image for the input and
output data cannot exceed 500 bytes in each case.
Example of total length:
If the individual I/O modules have a width of 12 mm, 64 modules may be
connected, but if they are 24 mm wide, then only 32 I/O modules may be
connected.
With the optional WAGO internal data bus extension (consisting of the 750-628
Coupler Module and 750-627 End Module), it is possible to use up to 250
I/O modules. The same limitations apply in this case as for the use of 64
I/O modules.
Using the WAGO internal data bus extension
Information on the use of the WAGO internal data bus extension can be found in
the 750-627 and 750-628 documentation, which can be obtained from the WAGO
internet site.
Additional information and application instructions for use of WAGO
Terminals
Additional information and instructions for use for WAGO I/O modules can be
found in the WAGO-I/O-SYSTEM 750/753 system description. The respective
manuals and data sheets can be found at www.wago.com.