Table 142: Description of the configuration scripts for " General SNMP information parameters "
Parameter
IP Address of a
Trap Receiver
Community
Name
Trap Version
Creating/
deleting a trap
receiver
Status Call
get_snmp_data
read
v1-v2c-trap-receiver-
address <number>
get_snmp_data
v1-v2c-trap-receiver-
read
community-name
<number>
get_snmp_data
read
v1-v2c-trap-receiver-
version <number>
config_snmp
v1-v2c-trap-receiver-
edit=<value1>
v1-v2c-trap-receiver-
address=<value2>
write
v1-v2c-trap-receiver-
community-
name=<value3>
v1-v2c-trap-receiver-
version=<value4>
WAGO-I/O-SYSTEM 750
758-874/000-131 WAGO-I/O-IPC-C6
Output/Input
Specifies the IP address of
the trap receiver, to which
the I/O-IPC should send the
v1 or v2 traps.
The <number> parameter
serves to enable
consecutive reading of the
related data from the
individually configured trap
receiver for a short period
of time (without interim
changing of the data). This
is a running number that is
not connected to the data. If
the number is not included,
the data of the first receiver
are read.
Specifies the community
name that the SNMP agent
of the IPC sends in the Trap
Header.
Parameter <number>, see
section "IP Address of a
Trap Receiver".
Specifies the SNMP
version ("v1" or "v2c") via
which the SNMP agent
sends the traps to the
associated trap receiver
address.
Parameter <number>, see
section "IP Address of a
Trap Receiver".
Create a new trap receiver
(value1=add) or delete an
already configured trap
receiver (value1=delete).
Additional parameters:
<value2> = IP address
(number.number.number.
number), to which the IPC
should send the traps.
<value3>: community
string (string), which the
IPC enters into the trap
header.
<value4>: SNMP version,
via which the traps are sent
(v1 or v2c).
Note:
When deleting a trap
receiver, all parameters
must also be entered, as this
is the only means to
uniquely identify the data
set.
Validity
immediate
after restart