Event code
Event name
54011806 hex
Packet Monitoring
Function Not
Started
54011807 hex
Packet Monitoring
Function in Opera-
tion
54011808 hex
Communications
Resource Overflow
54011809 hex
Packet Monitoring
Function Not Sup-
ported
54011C00 hex
Explicit Message
Error
54011C01 hex
Incorrect Route
Path
54011C02 hex
CIP Handle Out of
Range
NY-series Troubleshooting Manual (W564)
Meaning
A Stop EtherCAT Packet
• A Stop EtherCAT
Monitor instruction was
executed when EtherCAT
packet monitoring was
stopped.
A Start EtherCAT Packet
• The Start EtherCAT
Monitor instruction was
executed when EtherCAT
packet monitoring was
already being executed.
More than 32 EtherCAT
• More than 32 Ether-
communications instruc-
tions were executed at the
same time.
Packets cannot be moni-
• An instruction for
tored.
An error response code
• Depends on the
was returned for an explicit
message that was sent with
a CIP communications
instruction.
The format of the route
• The format of the
path that is specified for a
CIP communications
instruction is not correct.
• The handle that is
The handle that is specified
for the CIP communications
instruction is not correct.
3 Error Descriptions and Corrections
Assumed cause
Maj
Prt
Packet Monitor
instruction was exe-
cuted when EtherCAT
packet monitoring was
stopped.
Packet Monitor
instruction was exe-
cuted again while the
EtherCAT packet
monitoring function
was already in opera-
tion.
CAT communications
instructions were exe-
cuted at the same
time. The EtherCAT
communications
instructions are listed
below.
• EC_CoESDOWrite
instruction
• EC_CoESDORead
instruction
• EC_ConnectSlave
instruction
• EC_Disconnect-
Slave instruction
• EC_StartMon
instruction
• EC_SaveMon
instruction
• EC_StopMon
instruction
• EC_CopyMon
instruction
packet monitoring was
executed for a CPU
Unit that does not sup-
port packet monitor-
ing.
nature of the error.
route path that is
specified for a CIP
communications
instruction is not cor-
rect.
specified for the CIP
communications
instruction is not cor-
rect.
Level
Refer-
ence
Min
Obs
Info
S
page 3-139
S
page 3-140
S
page 3-141
S
page 3-142
S
page 3-143
S
page 3-144
S
page 3-144
3-19
3