1 Overview of Errors
1-2

Fatal Errors

1-2-1

Types of Fatal Errors

This section describes the errors that cause the operation of the NY-series Controller to stop.
Software connections to the Sysmac Studio or an HMI cannot be made if there is a fatal error in the NY-
series Controller.
Error
Error during Industrial PC System
Boot
Power Supply Error
CPU Unit Reset
CPU Unit Error
System Initialization Error
1-2-2

Checking for Fatal Errors

You can identify fatal errors in the NY-series Controller based on the status of the PWR, RUN and ERR
indicators, the monitor display, as well as by the possibility to go online from the Sysmac Studio. Refer
to Section 2 Error Troubleshooting Methods for information on identifying errors and corrections.
PWR (green)
Lit
Not lit
Lit
Lit
Lit
*1 An online connection to the Sysmac Studio is necessary to differentiate between CPU Unit Resets, CPU Unit
Errors, and non-fatal errors in the NY-series Controller. For an OS Startup Error, an error message is displayed
on the monitor screen. Power Supply Errors and System Initialization Errors can be differentiated with the in-
dicators. There is no need to see if you can go online with the NY-series Controller from the Sysmac Studio.
1-6
The NY-series Industrial PC cannot start up correctly due to an error that
occurred before the Controller starts up (e.g. during BIOS startup or before
OS startup).
Power is not supplied, or the voltage is outside of the allowed range.
The NY-series Controller stops operation because of a hardware error.
This error can occur for an NY-series Industrial PC. It indicates that there
is a hardware failure or that the CPU is running out of control due to tem-
porary data corruption.
This error can occur for an NY-series Industrial PC. It indicates a hardware
failure.
The RUN indicator flashes at 2-second intervals while the NY-series Indus-
trial PC is starting, but if it flashes for 30 seconds or longer, then this error
occurs.
Indicators
ERR (red)
RUN (green)
Not lit or lit
Not lit
Not lit
Not lit
Not lit
Not lit
Lit
Not lit or
Flashing (2-s
intervals or
0.5-s inter-
vals)
Not lit
Flashing (2-s
intervals) for
30 s or longer
Description
Communica-
Monitor display
tions with Sys-
mac Studio
Error message
Not possible.
---
---
---
---
NY-series Troubleshooting Manual (W564)
NY-series Industrial
PC operating status
*1
Error during Industrial
PC System Boot
Power Supply Error
CPU Unit Reset
CPU Unit Error
System Initialization
Error