Omron NY532-5400 Troubleshooting Manual page 617

Ny-series
Hide thumbs Also See for NY532-5400:
Table of Contents

Advertisement

Event name
Controller Insufficient Memory Warning
The amount of data for the EtherCAT slave configuration, network-published information, or other data
Meaning
exceeds the value that is specified for the CPU Unit. You may not be able to perform online editing or
other operations.
EtherCAT Master Function Mod-
Source
ule or EtherNet/IP Function Mod-
ule
Error attri-
Level
butes
Effects
User program
EtherCAT NET RUN
Indicators
---
System-
Variable
defined
None
variables
Assumed cause
The amount of data for the Ether-
CAT slave configuration, network-
Cause and
published information, or other
correction
data exceeds the value that is
specified for the CPU Unit.
Attached
None
information
Precautions/
You may not be able to perform online editing or other operations.
Remarks
NY-series Troubleshooting Manual (W564)
Source details
Minor fault
Recovery
Continues.
Operation
EtherCAT NET ERR
---
Data type
---
Correction
Reduce the number of PDOs that
are used by the EtherCAT slaves.
Reduce the number of data types
that are used for network vari-
ables or reduce the length of the
text strings that are used for
names.
3 Error Descriptions and Corrections
Event code
50010000 hex
Master or CIP
Detection
timing
Error reset
Log category
Not affected.
EtherCAT LINK/ACT
---
Name
---
Prevention
None
At power ON,
download, or
online editing
System
3
3-541