3 Error Descriptions and Corrections
Event code
Event name
60050000 hex
Task Period
Exceeded
Errors Related to Controller Operation
Event code
Event name
10200000 hex
User Pro-
gram/Con-
troller
Configura-
tions and
Setup Trans-
fer Error
10210000 hex
Illegal User
Program
Execution ID
10240000 hex
Illegal User
Program
10250000 hex
Illegal User
Pro-
gram/Con-
troller
Configura-
tions and
Setup
4011 0000 hex
PLC Function
Processing
Error
3-8
Meaning
Assumed cause
Task execution was
• The task period setting is too
not completed
short.
during the set task
• A user program is too large.
period for the pri-
• The number of times that pro-
mary periodic task
cessing is repeated is larger
or fixed periodic
than expected.
task.
• Task Priority Error for Periodic
Tasks and Event Tasks
• Frequent Event Task Execution
Meaning
Assumed cause
The user program
• The user program or Controller
or Controller Con-
Configurations and Setup are
figurations and
not correct because the power
Setup were not
supply to the Controller was
transferred cor-
interrupted during a download
rectly.
of the user program or the Con-
troller Configurations and
Setup.
• The user program or Controller
Configurations and Setup are
not correct because the power
supply to the Controller was
interrupted during online edit-
ing.
• The user program or Controller
Configurations and Setup are
not correct because the power
supply to the Controller was
interrupted during a Clear All
Memory operation.
• The user program or Controller
Configurations and Setup are
not correct because the power
supply to the Controller was
interrupted during a restore
operation.
• Non-volatile memory failed.
The user program
• The user program execution
execution IDs set in
IDs set in the user program and
the user program
in the CPU Unit do not match.
and in the CPU Unit
• A user program execution ID is
do not match.
set in the CPU Unit but not in
the user program.
The user program
• There are more than 8 nesting
is not correct.
levels for functions or function
blocks.
The upper limit of
• The upper limit of the data size
the usable memory
was exceeded.
was exceeded or
• The main memory capacity was
the user program or
exceeded.
Controller Configu-
• Non-volatile memory is deterio-
rations and Setup is
rating or has failed.
corrupted.
A fatal error was
• An error occurred in the soft-
detected in the PLC
ware.
Function Module.
Level
Maj
Prt
Min
Obs Info
S
page 3-66
Level
Maj
Prt
Min
Obs Info
S
page 3-67
S
page 3-68
S
page 3-69
S
page 3-70
S
page 3-71
NY-series Troubleshooting Manual (W564)