3 Error Descriptions and Corrections
Event code
Event name
84230000 hex
Slave Initial-
ization Error
84280000 hex
Slave Appli-
cation Error
84290000 hex
Process Data
Transmis-
sion Error
842B0000 hex
Process Data
Reception
Timeout
842C 0000 hex
Process Data
Communica-
tions Error
3-530
Meaning
Assumed cause
Slave initialization
• An error occurred in EtherCAT
failed.
master processing.
• An initialization error occurred
in the EtherCAT slave.
• An initialization error occurred
in the EtherCAT Coupler Unit.
• A major fault level Controller
error occurred.
• The Ethernet cable is broken or
the specified cable is not being
used.
• A connector on the Ethernet
cable is disconnected, the con-
tact is faulty, or parts are faulty.
• A general-purpose Ethernet
hub is connected.
• The master failed.
• The slave failed.
• Noise.
An error occurred in
• An error was detected in the
the slave applica-
slave's application layer status
tion.
register.
Sending process
• It was not possible to send the
data failed.
EtherCAT frame during the Eth-
erCAT communications period.
• The frame transmission jitter
exceeded the limit.
Process data
• The Ethernet cable is broken or
reception timed out.
the specified cable is not being
used.
• A connector on the Ethernet
cable is disconnected, the con-
tact is faulty, or parts are faulty.
• A general-purpose Ethernet
hub is connected.
• The master failed.
• The slave failed.
• The Ethernet cable is too long.
• The CPU Unit task period is too
short.
• Noise
An error occurred in
• A slave left the network even
process data com-
though the disconnection oper-
munications.
ation or disable operation was
not performed.
• The slave failed.
Level
Maj
Prt
Min
Obs Info
S
page 3-546
S
page 3-548
S
page 3-549
S
page 3-550
S
page 3-552
NY-series Troubleshooting Manual (W564)