3 Error Descriptions and Corrections
Event name
Packet Monitoring Function Not Supported
Meaning
Packets cannot be monitored.
PLC Function Module
Source
Error attri-
Level
butes
Effects
User program
System-
Variable
defined
None
variables
Assumed cause
An instruction for packet monitor-
ing was executed for a CPU Unit
Cause and
that does not support packet
correction
monitoring.
Attached Information 1: Error Location
Attached Information 2: Error Location Details (Rung Number). For a program section, the rung number
from the start of the section is given. For ST, the line number is given.
Attached
Attached Information 3: Names of the Instruction and Instruction Instance Where the Error Occurred. If
information
there is more than one possible instruction, information is given on all of them. Nothing is given if the
instruction cannot be identified.
Attached Information 4: Expansion Error Code (ErrorIDEx)
Precautions/
If a program is changed after an error occurs, the attached information that is displayed may not be cor-
Remarks
rect.
3-142
Source details
Observation
Recovery
Continues.
Operation
Data type
---
Correction
Do not execute the EC_StartMon,
EC_SaveMon, EC_StopMon, or
EC_CopyMon instruction. If
packet monitoring is required,
use a CPU Unit that supports
packet monitoring.
Event code
54011809 hex
Instruction
Detection
timing
---
Log category
The relevant instruction will end according to speci-
fications.
Name
---
Prevention
Do not execute instructions for
packet monitoring for a CPU Unit
that does not support packet
monitoring.
NY-series Troubleshooting Manual (W564)
At instruction
execution
System