Omron NY532-5400 Troubleshooting Manual page 150

Ny-series
Hide thumbs Also See for NY532-5400:
Table of Contents

Advertisement

3 Error Descriptions and Corrections
Event name
Trace Setting Transfer Failure
Meaning
The power supply was interrupted while transferring the trace settings.
PLC Function Module
Source
Error attri-
Level
butes
Effects
User program
System-
Variable
defined
None
variables
Assumed cause
Cause and
The power supply was inter-
correction
rupted while transferring the trace
settings.
Attached
None
information
Precautions/
All trace settings are initialized when this error occurs.
Remarks
3-74
Source details
Observation
Recovery
Continues.
Operation
Data type
---
Correction
Transfer the trace settings again.
Event code
1026 0000 hex
None
Detection
timing
Cycle the
power supply
Log category
or reset the
Controller.
Not affected.
Name
---
Prevention
Do not interrupt the power supply
while transferring the trace set-
tings.
NY-series Troubleshooting Manual (W564)