3 Error Descriptions and Corrections
Event name
Transition Mode Selection Out of Range
The parameter specified for the TransitionMode input variable to a motion control instruction is out of
Meaning
range.
PLC Function Module
Source
Error attri-
Level
butes
Effects
User program
Variable
System-
defined
_MC_GRP[*].MFaultLvl.Active
variables
Assumed cause
Instruction input parameter
exceeded the valid range of the
input variable.
_mcAborting or _mcBuffered was
specified for BufferMode and
Cause and
_mcTMCornerSuperimposed
correction
was specified for TransitionMode.
Attached Information 1: Error Location
Attached Information 2: Error Location Details (Rung Number). For a program section, the rung number
from the start of the section is given. For ST, the line number is given.
Attached
Attached Information 3: Names of the Instruction and Instruction Instance Where the Error Occurred. If
information
there is more than one possible instruction, information is given on all of them. Nothing is given if the
instruction cannot be identified.
Attached Information 4: Expansion Error Code (ErrorIDEx)
Precautions/
If a program is changed after an error occurs, the attached information that is displayed may not be cor-
Remarks
rect.
3-194
Source details
Observation
Recovery
Continues.
Operation
Data type
BOOL
Correction
Correct the parameter so that the
valid range of the input variable is
not exceeded for the relevant
instruction.
If you specify _mcAborting or
_mcBuffered for BufferMode,
specify _mcTMNone for Transi-
tionMode. If you specify _mcTM-
CornerSuperimposed for
TransitionMode, specify _mc-
BlendingLow, _mcBlendingPrevi-
ous, _mcBlendingNext, or
_mcBlendingHigh for Buffer-
Mode.
Event code
5401 5432 hex
Instruction
Detection
timing
---

Log category

The relevant instruction will end according to speci-
fications.
Name
Axes Group Minor Fault Occur-
rence
Prevention
Set the input parameter to the
instruction so that the valid range
of the input variable is not
exceeded.
If you specify _mcAborting or
_mcBuffered for BufferMode,
specify _mcTMNone for Transi-
tionMode. If you specify _mcTM-
CornerSuperimposed for
TransitionMode, specify _mc-
BlendingLow, _mcBlendingPrevi-
ous, _mcBlendingNext, or
_mcBlendingHigh for Buffer-
Mode.
NY-series Troubleshooting Manual (W564)