Omron NY532-5400 Troubleshooting Manual page 684

Ny-series
Hide thumbs Also See for NY532-5400:
Table of Contents

Advertisement

Appendix
NX-series Safety Control Units
The section provides tables of the errors (events) that can occur in the following Units.
NX-SL
NX-SI
NX-SO
The manual names are given below for the catalog numbers given in the Reference column of the
event table.
Cat. No.
Z930
 Safety CPU Units
Event code
Event name
05200000 hex
System Error
10500000 hex
NX Bus Com-
munications
Settings
Read Error
10510000 hex
Safety Appli-
cation Data
Read Error
10520000 hex
NX Bus Com-
munications
Settings and
Safety Appli-
cation Data
Mismatch
10530000 hex
Non-volatile
Memory
Access Error
35200000 hex
Safety Pro-
cess Data
Communica-
tions Not
Established
Error
55000000 hex
Division by
Zero
55010000 hex
Cast Error
55020000 hex
MUX Error
A-38
NX-series Safety Control Unit User's Manual
Meaning
Assumed cause
A hardware error
• Hardware has failed.
was detected
• A memory error occurred due to
during self-diagno-
a transient cause, such as a
sis of the hardware.
software error or excessive
noise.
There is an error in
• A hardware failure occurred in
the NX bus commu-
the non-volatile memory.
nications settings
• Power was turned OFF while
that are saved in
saving data to the non-volatile
non-volatile mem-
memory.
ory.
There is an error in
• A hardware failure occurred in
the safety applica-
the non-volatile memory.
tion data that is
• Power was turned OFF while
saved in non-vola-
saving data to the non-volatile
tile memory.
memory.
There is an error in
• The NX bus communications
the safety applica-
settings that were transferred to
tion data that is
the Safety CPU Unit do not
saved in non-vola-
match the safety application
tile memory.
data.
Reading/writing
Non-volatile memory failed.
non-volatile mem-
ory failed.
Safety process data
• The communications settings
communications
for safety process data are not
was not estab-
correct, the safety slave is not
lished with one or
in the correct status, etc.
more safety slaves.
• The safety slave for safety pro-
cess data communications is
not connected.
• The NX Unit Mounting Setting
for the safety slave for safety
process data communications
is set to Disabled.
Division by zero
The divisor is zero.
was detected.
A casting error was
A value was input that exceeded
detected.
the range of the receiving vari-
able.
An MUX instruction
The value of the selection input
error was detected.
(K) to the MUX instruction is not
correct.
Manual name
Level
Maj
Prt
Min
Obs Info
S
S
S
S
S
S
S
S
S
NY-series Troubleshooting Manual (W564)
Reference
Z930
Z930
Z930
Z930
Z930
Z930
Z930
Z930
Z930