Appendix
NX-series Safety Control Units
The section provides tables of the errors (events) that can occur in the following Units.
NX-SL
NX-SI
NX-SO
The manual names are given below for the catalog numbers given in the Reference column of the
event table.
Cat. No.
Z930
Safety CPU Units
Event code
Event name
05200000 hex
System Error
10500000 hex
NX Bus Com-
munications
Settings
Read Error
10510000 hex
Safety Appli-
cation Data
Read Error
10520000 hex
NX Bus Com-
munications
Settings and
Safety Appli-
cation Data
Mismatch
10530000 hex
Non-volatile
Memory
Access Error
35200000 hex
Safety Pro-
cess Data
Communica-
tions Not
Established
Error
55000000 hex
Division by
Zero
55010000 hex
Cast Error
55020000 hex
MUX Error
A-38
NX-series Safety Control Unit User's Manual
Meaning
Assumed cause
A hardware error
• Hardware has failed.
was detected
• A memory error occurred due to
during self-diagno-
a transient cause, such as a
sis of the hardware.
software error or excessive
noise.
There is an error in
• A hardware failure occurred in
the NX bus commu-
the non-volatile memory.
nications settings
• Power was turned OFF while
that are saved in
saving data to the non-volatile
non-volatile mem-
memory.
ory.
There is an error in
• A hardware failure occurred in
the safety applica-
the non-volatile memory.
tion data that is
• Power was turned OFF while
saved in non-vola-
saving data to the non-volatile
tile memory.
memory.
There is an error in
• The NX bus communications
the safety applica-
settings that were transferred to
tion data that is
the Safety CPU Unit do not
saved in non-vola-
match the safety application
tile memory.
data.
Reading/writing
Non-volatile memory failed.
non-volatile mem-
ory failed.
Safety process data
• The communications settings
communications
for safety process data are not
was not estab-
correct, the safety slave is not
lished with one or
in the correct status, etc.
more safety slaves.
• The safety slave for safety pro-
cess data communications is
not connected.
• The NX Unit Mounting Setting
for the safety slave for safety
process data communications
is set to Disabled.
Division by zero
The divisor is zero.
was detected.
A casting error was
A value was input that exceeded
detected.
the range of the receiving vari-
able.
An MUX instruction
The value of the selection input
error was detected.
(K) to the MUX instruction is not
correct.
Manual name
Level
Maj
Prt
Min
Obs Info
S
S
S
S
S
S
S
S
S
NY-series Troubleshooting Manual (W564)
Reference
Z930
Z930
Z930
Z930
Z930
Z930
Z930
Z930
Z930