Event code
Event name
848F0000 hex
Device Con-
figuration Veri-
fication Error
84970000 hex
I/O Cable
Short-circuit
849A0000 hex
IO-Link Com-
munications
Module Pro-
cessing Error
80220000 hex
NX Message
Communica-
tions Error
848C0000 hex
Error-level
Device Event
848D0000 hex
IO-Link Com-
munications
Error
84990000 hex
Warning-level
Device Event
Flag
84950000 hex
IO-Link
Device Con-
figuration
Information
Created
84980000 hex
I/O Power
Supply ON
Detected
90400000 hex
Event Log
Cleared
A-48
Meaning
Assumed cause
The connected
The connected device is
device is different
different from the IO-Link
from the IO-Link
device registered for a
device registered for
port of the IO-Link Master.
a port of the IO-Link
Master.
There is a short-cir-
There is a short-circuit in
cuit in the cable that
the I/O cable.
connects the IO-
An IO-Link device has
Link master and
failed.
device.
A hardware failure
A hardware failure
occurred in the IO-
occurred.
Link Communica-
tions Module.
An error was
For the NX bus of CPU
detected in mes-
Units
sage communica-
• The message communi-
tions and the
cations load is high.
message frame was
For Communications Cou-
discarded.
pler Units
• The message communi-
cations load is high.
• The communications
cable is disconnected or
broken.
• Message communica-
tions were cutoff in com-
munications.
An error-level event
Use CX-Configurator FDT
occurred in the IO-
to confirm the event code
Link device.
of the IO-Link device.
An error occurred in
The I/O cable is broken.
IO-Link communica-
Or, the IO-Link device is
tions with a device.
disconnected from the
port.
The communications were
affected by noise or IO-
Link device failure.
A warning-level
Use CX-Configurator FDT
event occurred in
to confirm the event code
the IO-Link device.
of the IO-Link device.
IO-Link device con-
IO-Link device configura-
figuration informa-
tion information was cre-
tion was created.
ated.
The I/O power sup-
The I/O power supply ON
was detected in several
ply ON was
times.
detected in several
times.
The event log was
• The event log was
cleared.
cleared by the user.
Level
Maj
Prt
Min
Obs
Info
S
S
S
S
S
S
S
S
S
S