Omron NY532-5400 Troubleshooting Manual page 149

Ny-series
Hide thumbs Also See for NY532-5400:
Table of Contents

Advertisement

Event name
Event Log Save Error
Meaning
Saving the event log failed.
PLC Function Module
Source
Error attri-
Level
butes
Effects
User program
System-
Variable
defined
None
variables
Assumed cause
A low battery voltage prevented
retention of memory during a
power interruption. (NJ/NX-
series)
A forced shutdown was per-
formed. (NY-series)
Data in the event log area are
Cause and
invalid. (NY-series)
correction
Data in the NX Unit event log
area are invalid. (NX1P2 CPU
Unit)
Attached information 1: Error Details
0: Failure to save all categories of logs,
Attached
1: Failure to save system event log,
information
2: Failure to save access event log,
100: Failure to save user-defined event log
Precautions/
None
Remarks
NY-series Troubleshooting Manual (W564)
Source details
Observation
Recovery
Starts.
Operation
Data type
---
Correction
Replace the Battery.
None
If the error persists even after you
cycle the power to the Industrial
PC, a hardware failure may occur
in the event log area. Replace the
Industrial PC if you use the event
logs in the Industrial PC.
If this error persists even after
you cycle the power supply to the
CPU Unit, a hardware failure may
occur in the event log area.
Replace the CPU Unit if you use
the event logs in the CPU Unit.
3 Error Descriptions and Corrections
Event code
10230000 hex
None
Detection
timing
---
Log category
Not affected. However, part or all of the past event
log cannot be read.
Name
---
Prevention
Replace the battery periodically.
Perform a shutdown with other
method than the forced shut-
down.
None
None
At power ON or
Controller reset
System
3
3-73