3 Error Descriptions and Corrections
Event code
Event name
54300000 hex
Position Type
Selection Out
of Range
54310000 hex
Travel Mode
Selection Out
of Range
54320000 hex
Transition
Mode Selec-
tion Out of
Range
54330000 hex
Continue
Method
Selection Out
of Range
54340000 hex
Combine
Mode Selec-
tion Out of
Range
54350000 hex
Synchroniza-
tion Start
Condition
Selection Out
of Range
54360000 hex
Master and
Slave
Defined as
Same Axis
54370000 hex
Master and
Auxiliary
Defined as
Same Axis
54380000 hex
Mas-
ter/Slave
Axis Num-
bers Not in
Ascending
Order
3-328
Meaning
Assumed cause
The parameter
• Instruction input parameter
specified for the
exceeded the valid range of the
ReferenceType
input variable.
input variable to a
motion control
instruction is out of
range.
The parameter
• Instruction input parameter
specified for the
exceeded the valid range of the
MoveMode input
input variable.
variable to a motion
control instruction is
out of range.
The parameter
• Instruction input parameter
specified for the
exceeded the valid range of the
TransitionMode
input variable.
input variable to a
• _mcAborting or _mcBuffered
motion control
was specified for BufferMode
instruction is out of
and _mcTMCornerSuperim-
range.
posed was specified for Transi-
tionMode.
The value of the
• The value of the reserved input
reserved input vari-
variable Continuous changed.
able Continuous to
a motion control
instruction
changed.
The parameter
• Instruction input parameter
specified for the
exceeded the valid range of the
CombineMode
input variable.
input variable to a
motion control
instruction is out of
range.
The parameter
• Instruction input parameter
specified for the
exceeded the valid range of the
LinkOption input
input variable.
variable to a motion
control instruction is
out of range.
The same axis is
• The parameter is the same for
specified for the
the Master and Slave input vari-
Master and Slave
ables to the instruction.
input variables to a
motion control
instruction.
The same axis is
• The parameter is the same for
specified for the
the Master and Auxiliary input
Master and Auxil-
variables to the instruction.
iary input variables
to a motion control
instruction.
The axis numbers
• The parameters for the Master
specified for the
and Slave input variables to the
Master and Slave
instruction were not in ascend-
input variables to a
ing order when _mcLatestCom-
motion control
mand was specified for the
instruction are not
ReferenceType input variable to
in ascending order.
the instruction.
Level
Maj
Prt
Min
Obs Info
S
page 3-398
S
page 3-399
S
page 3-400
S
page 3-400
S
page 3-401
S
page 3-401
S
page 3-402
S
page 3-402
S
page 3-403
NY-series Troubleshooting Manual (W564)
Reference

Advertisement

Table of Contents
loading