inverters
Goodrive300
Functio
Name
n code
frequency
point 2
Motor 2V/F
P04.19
voltage point
2
Motor 2V/F
P04.20
frequency
point 3
Motor 2V/F
P04.21
voltage point
3
Motor 2 V/F
slip
P04.22
compensatio
n gain
Motor 2 low
frequency
P04.23
vibration
control factor
Motor 2 high
frequency
P04.24
vibration
control factor
Motor 2
vibration
P04.25
control
threshold
Energy-savin
P04.26
g operation
selection
Voltage
P04.27
Setting
Channel
Detailed instruction of parameters
In the V/F control mode, current fluctuation may
occur to the motor on some frequency, especially the
motor with big power. The motor can not run stably
or overcurrent may occur. These phenomena can be
canceled by adjusting this parameter.
The setting range of P04.23:0~100
The setting range of P04.24:0~100
The setting range of P04.25:0.00Hz~P00.03(the
Max. frequency)
0:No operation
1:Automatic energy-saving operation
Motor on the light load conditions, automatically
adjusts the output voltage to save energy
Select the output setting channel at V/F curve
separation.
0: Keypad setting voltage: the output voltage is
76
Function codes
Default
Modif
value
y
z
○
00.0%
00.00H
○
z
○
00.0%
○
0.0%
○
10
○
10
30.00
○
Hz
◎
0
○
0
Need help?
Do you have a question about the Goodrive 300 and is the answer not in the manual?
Questions and answers