inverters
Goodrive300
Function
code
Torque given filter
P03.13
Torque control
forward
P03.14
upper-limit
frequency setting
source selection
Torque control
P03.15
reverse
upper-limit
Name
0.000~10.000s
time
0:Keypad setting upper-limit frequency(P03.16)
1:Analog AI1 setting upper-limit frequency
(100% corresponds to the max. frequency)
2:Analog AI2 setting upper-limit
frequency(100% corresponds to the max.
frequency)
3:Analog AI3 setting upper-limit
frequency(100% corresponds to the max.
frequency)
4:Pulse frequency HDI setting upper-limit
frequency(100% corresponds to the max.
frequency)
rotation
5:Multi-stage setting upper-limit
frequency(100% corresponds to the max.
frequency)
6:MODBUS communication setting upper-limit
frequency(100% corresponds to the max.
frequency)
7:PROFIBUS communication setting upper-limit
frequency (100% corresponds to the max.
frequency)
8:Ethernet communication setting upper-limit
frequency (100% corresponds to the max.
frequency)
9:CAN communication setting upper-limit
frequency(100% corresponds to the max.
frequency)
0:Keypad setting upper-limit frequency(P03.17)
rotation
1:Analog AI1 setting upper-limit frequency
(100% corresponds to the max. frequency)
Detailed instruction of parameters
159
Basic operation instruction
Default
value
0
0
0
Need help?