inverters
Goodrive300
Functio
Name
n code
Cooling fan
P08.39
running
mode
PWM
P08.40
selection
Over
P08.41
commission
selection
Keypad data
P08.42
control
Detailed instruction of parameters
level.
The setting range:200.0~2000.0V
0:Rated running mode
1:The fan keeps on running after power on
LED ones: PWM mode selection
0: PWM mode 1, three-phase modulation and
two-modulation
1: PWM mode 2, three-phase modulation
LED tens: low-speed carrier frequency limit mode
0: Low-speed carrier frequency limit mode 1, the
carrier frequency will limit to 2k if it exceeds 2k at low
speed
1:Low-speed carrier frequency limit mode 2, the
carrier frequency will limit to 4k if it exceeds 4k at low
speed
2: No limit
0:Invalid
1:Valid
0x000~0x1223
LED ones:frequency enable selection
0:Both ∧/∨ keys and digital potentiometer
adjustments are effective
1:Only ∧/∨ keys adjustments is effective
2:Only digital potentiometer adjustments is effective
3:Neither ∧/∨ keys nor digital potentiometer
adjustments are effective
107
Function codes
Default
Modif
value
y
380V
voltage:7
00.0V
660V
voltage:1
120.0V
○
0
◎
01
◎
1
○
0x0000
Need help?