n code
Overload
pre-alarm of
P11.08
the
motor/inverte
r
Overload
P11.09
pre-alarm
test level
Overload
pre-alarm
P11.10
detection
time
Detailed instruction of parameters
to run.
Setting range of P11.05:
0:current limit invalid
1:current limit valid
2:current limit is invalid during constant speed
Setting range of P11.06:50.0~200.0%
Setting range of P11.07:0.00~50.00Hz/s
The output current of the inverter or the motor is
above P11.09 and the lasting time is beyond P11.10,
overload pre-alarm will be output.
Setting range of P11.08:
Enable and define the overload pre-alarm of the
inverter or the motor.
Setting range: 0x000~0x131
LED ones:
0:Overload pre-alarm of the motor, comply with the
121
Function codes
Default
Modif
value
y
0x000
150%
1.0s