P01.18
when
powering on
The running
frequency is
lower than
the lower
P01.19
limit one
(valid if the
lower limit
frequency is
above 0)
Detailed instruction of parameters
will stop after the set time of P01.17.
Setting range:0.0~100.0s (only valid when
P01.16=1)
When the running command channel is the terminal
control, the system will detect the state of the
running terminal during powering on.
0:The terminal running command is invalid when
powering on. Even the running command is detected
to be valid during powering on, the inverter won't run
and the system keeps in the protection state until the
running command is canceled and enabled again.
1: The terminal running command is valid when
powering on. If the running command is detected to
be valid during powering on, the system will start the
inverter automatically after the initialization.
Note: this function should be selected with cautions,
or serious result may follow.
This function code determines the running state of
the inverter when the set frequency is lower than the
lower-limit one.
0: Run at the lower-limit frequency
1: Stop
2: Hibernation
The inverter will coast to stop when the set
frequency is lower than the lower-limit one.if the set
frequency is above the lower limit one again and it
lasts for the time set by P01.20, the inverter will
60
Function codes
Default
Modif
value
y
0
0