inverters
Goodrive300
Functio
Name
n code
Keypad set
P00.10
frequency
P00.11 ACC time 1
P00.12 DEC time 1
Running
P00.13
direction
Detailed instruction of parameters
P5(terminal function)
When A and B frequency commands are selected as
"keypad setting", the value of the function code is the
original setting one of the frequency data of the
inverter.
Setting range:0.00 Hz~P00.03(the Max. frequency)
ACC time means the time needed if the inverter
speeds up from 0Hz to the Max. One (P00.03).
DEC time means the time needed if the inverter
speeds down from the Max. Output frequency to 0Hz
(P00.03).
Goodrive300 series inverters define four groups of
ACC/DEC time which can be selected by P05. The
factory default ACC/DEC time of the inverter is the
first group.
Setting range of P00.11 and P00.12:0.0~3600.0s
0: Runs at the default direction, the inverter runs in
the forward direction. FWD/REV indicator is off.
1:Runs at the oppositing direction, the inverter runs
in the reverse direction. FWD/REV indicator is on.
Modify the function code to shift the rotation direction
of the motor. This effect equals to the shifting the
rotation direction by adjusting either two of the motor
lines (U, V and W). The motor rotation direction can
be changed by QUICK/JOG on the keypad. Refer to
parameter P07.02.
Note: When the function parameter comes back to
the default value, the motor's running direction will
come back to the factory default state, too. In some
cases it should be used with caution after
commissioning if the change of rotation direction is
disabled.
2: Forbid to run in reverse direction: It can be used in
53
Function codes
Default
Modif
value
y
50.00H
○
z
Depend
○
on
model
Depend
○
on
model
○
0
Need help?
Do you have a question about the Goodrive 300 and is the answer not in the manual?
Questions and answers