inverters
Goodrive300
Functio
Name
n code
counting
value
Set running
P08.27
time
Fault reset
P08.28
times
Interval time
P08.29
of automatic
fault reset
Frequency
P08.30
decreasing
ratio of the
Detailed instruction of parameters
of "fixed counting number arrival" and the counter go
on working; when the counter achieves a setting
number, the multi-function output terminals will
output the signal of "setting counting number arrival",
the counter will clear all numbers and stop to recount
before the next pulse.
The setting counting value P08.26 should be no
more than the setting counting value P08.25.
The function is illustrated as below:
Setting range of P08.25:P08.26~65535
Setting range of P08.26:0~P08.25
Pre-set running time of the inverter. When the
accumulative running time achieves the set time, the
multi-function digital output terminals will output the
signal of "running time arrival".
Setting range:0~65535m
The time of the fault reset: the inverter set the fault
reset time by selecting this function. If the reset time
exceeds this set value, the inverter will stop for the
fault and wait to be repaired.
The interval time of the fault reset: the interval
between the time when the fault occurs and the time
when the reset action occurs.
Setting range of P08.28:0~10
Setting range of P08.29:0.1~3600.0s
The output frequency of the inverter changes as the
load. And it is mainly used to balance the power
when several inverters drive one load.
104
Function codes
Default
Modif
value
y
○
0m
○
0
○
1.0s
○
0.00Hz