10.12 EZPID (PID Operation: PWM Output Available)

Ladder diagram
List of operands
Operand
Description
S1
1-word area for setting control data that determine methods for auto-tuning and output
S2
1-word area for inputting the process value (PV)
4-word area for setting the set point value (SV), proportional gain (Kp), integral time (Ti), and
S3
derivative time (Td).
30-word area comprising the following:
S4
Storage area for the manipulated value (MV), control interval (Ts), control mode, setting area for
parameters related to auto-tuning, and operation work area
Devices that can be specified (indicated by ●)
Operan
d
W
W
X
Y
S1
S2
S3
S4
Outline of operation
● PID operation is carried out to retain the process value (PV) stored in [S+2], in consistency
with the set point value (SP) specified by [S3].
● The operation result is stored, as a manipulated value (MV), in the area specified by [S4]. If
an OUT instruction is described immediately after this instruction, PWM output (ON-OFF
output) can be gained, proportionate to the manipulated value.
● Set the parameters used for PID operation (proportional gain, integral time, and derivative
time) to [S3+1] to [S3+3]. The auto-tuning function for automatically calculating these values
is also available.
● To change the method for PID operation (derivative-first operation/proportional-plus-
derivative-first operation, reverse operation/forward operation) or the control interval Ts, etc.,
set them to the area [S4] to [S4+9].
WUME-FP7CPUPGR-12
10.12 EZPID (PID Operation: PWM Output Available)
16-Bit device:
W
W
W
S
D
L
R
L
S
D
T
D
32-Bit
device:
TS
TE
U
W
WI
IX
C
C
M
O
S
E
Real
St
Integer
numbe
rin
r
g
D
K
H
SF
" "
F
Index
modifie
r
10-45

Advertisement

Table of Contents
loading

Table of Contents