Tm (Timer) - Panasonic FP7 Series Command Reference Manual

Cpu unit
Hide thumbs Also See for FP7 Series:
Table of Contents

Advertisement

3.17 TM (Timer)

3.17 TM (Timer)

Ladder diagram
List of operands
Operand
Description
n
Timer number
S
Timer set value
Devices that can be specified (indicated by ●)
Ope-
rand
WX WY WR WL WS SD DT LD UM WI WO
n
S
(Note 1)
Only TS can be specified for TM instruction.
(Note 2)
Only 16-bit devices, 32-bit devices, and integer constants can be modified. (Real number constants,
and character constants cannot be specified.)
Outline of operation
● The timer is the non-hold type that is reset when the power is turned off or the operation
mode is switched from RUN to PROG.
● When the execution condition is ON, the timer starts decrementing from the set time [S].
When the elapsed value reaches 0, the timer contact [Tn] (n is the timer contact number)
turns ON.
● When the execution condition turns OFF while the timer is decrementing, the timer stops and
resets the elapsed value (clears it to zero).
● The OT instruction can also be written immediately after a timer coil.
3-36
16-Bit device:
32-Bit
device:
TS
CS
(Note
1)
Real
Integer
number
TE
IX K U H SF DF
CE
WUME-FP7CPUPGR-12
Str-
ing Index
mod-
ifier
(Note
" "
2)

Advertisement

Table of Contents
loading