15.9 PMGET (Acquiring SCU Parameters)
Storage
locatio
Items
n
[D+3]
Transmission error flag
Transmission
[D+4]
assurance flag by
station
Station PLCs
[D+5]
Operation mode flag
Station PLCs
[D+6]
Operation state flag
[D+7]
Area overlap flag
Acquired data (PLC link error frequency information): When [S] = 3
Storage
locatio
Items
n
[D]
Number of lost tokens
Number of duplicate
[D+1]
tokens
Number of no signal
[D+2]
states
Number of times of
[D+3]
receptions of
undefined commands
Number of sum check
[D+4]
errors for reception
Number of received
[D+5]
data format errors
Number of
[D+6]
transmission errors
Number of procedural
[D+7]
errors
Number of duplicate
[D+8]
parent units
15-62
Range:
Description
Bit 6: Transmission error (0 = Normal, 1 = Error)
Bit 7: Procedural error (0 = Normal, 1 = Error)
Bit 15 to 8: Not used
Bit 0: Link 0 (0 = Normal, 1 = Error)
H0000 to
Bit 1: Link 1 (0 = Normal, 1 = Error)
H0003
Bit 15 to 2: Not used
Bit 0: Station number 1 (0: Stop, Error state, 1: Normal
transmission state)
H0000 to
:
H00FF
Bit 15: Station number 16 (0: Stop, Error state, 1: Normal
transmission state)
Bit 0: Station number 1 (0: PROG mode, 1: RUN mode)
H0000 to
:
H00FF
Bit 15: Station number 16 (0: PROG mode, 1: RUN mode)
Bit 0: Station number 1 (0: Normal, 1: Error)
H0000 to
:
H00FF
Bit 15: Station number 16 (0: Normal, 1: Error)
Bit 0: Station number 1 (0: Normal, 1: Area overlap occurs
(Position of partner unit is ON.)
H0000 to
:
H00FF
Bit 15: Station number 16 (0: Normal, 1: Area overlap occurs
(Position of partner unit is ON.)
Range:
Description
U0 to
The number of occurrences of each error is stored.
U65535
WUME-FP7CPUPGR-12