17.17 HTTPcSET (HTTP Client Transfer Setting)
Operand [S3] setting (UPLOAD operation for a device)
● Specify the starting address of the device area that stores the string data that indicates
source device settings, or a character constant.
Setting
Settings
item
Source device
setting
S3
Number of
transferred data
(number of bytes)
(Note 1)
Input each source device setting parameter separated by a comma ",".
(Note 2)
Specify the operation setting parameters in the order of the above table.
Setting example
Exam
S3
"WX16,32"
ple 1
Device setting, Device division: Global, Device code: WX, Device number: 16, Number of bytes:
Settings
32 bytes
Exam
S3
"DT123456,250"
ple 2
Device setting, Device division: Global, Device code: DT, Device number: 123456, Number of
Settings
bytes: 250 bytes
Exam
S3
"WR0,64"
ple 3
Device setting, Device division: Global, Device code: WR, Device number: 0, Number of bytes: 64
Settings
bytes
Exam
S3
"WL10,128"
ple 4
Device setting, Device division: Global, Device code: WL, Device number: 10, Number of bytes:
Settings
128 bytes
17-90
Specify the source device setting.
● Global devices
Specify device code + device number.
● Local devices
"PB" + PB number + "_" (underscore) + device code +
device number
Devices that can be specified
Global devices
WX
WY
WR
WL
DT
LD
Specify the number of transferred data (number of bytes). (1
to 7 digits)
* The number of bytes that can be simultaneously transferred
is 1 MB for all 16 IDs.
Local devices
WX
WY
WR
WL
DT
LD
WUME-FP7CPUPGR-12
Setting range
1 to 1048576
(1MB)