Panasonic FP7 Series Command Reference Manual page 788

Cpu unit
Hide thumbs Also See for FP7 Series:
Table of Contents

Advertisement

14.35 EMIDR (Data Read from a Given Position in the String: With Storage
Area Size)
(a)
Area in which the string to be taken out is stored
(1)
Storage area size
Precautions for programming
● When the number of characters of [S3] is larger than the number of characters of the [S1]
string starting from the [S2] position, the transferal is performed for the number of characters
of [S1].
● The [S2] position should be specified by a number counted from low order in sequence,
putting the least significant byte as K0 (Byte 0): 0, 1, 2 and so on.
● When the number of characters in the operation result is larger than the storage area size of
[D], the transferal is performed for the storage area size of [D].
● When specifying with a character constant, the maximum is 256 characters.
● When specifying an empty string for [S1], the result is always 0.
Flag operations
Name
SR7
SR8
(ER)
SR9 (CY)
14-138
Description
To be set in the case of out-of-range in indirect access (index modification).
To be set when the destination range is outside the accessible range.
To be set when the number of characters for [S1] is smaller than or equal to [S2].
To be set when the number of characters is larger than the storage area size for [S1].
To be set when a data table with a storage area size of 0 or 65535 is specified.
To be set when the number of characters taken out is larger than the storage area size of
[D].
Area in which the string that is taken out is
(b)
stored
(2)
Character count
WUME-FP7CPUPGR-12