Panasonic FP7 Series Command Reference Manual page 188

Cpu unit
Hide thumbs Also See for FP7 Series:
Table of Contents

Advertisement

3.26 JP/LBL (Jump/Label)
X100
X101
DF
<Timing Chart 1>
X100
X101
Y110
Final timing with no
execution of the last
JP instruction
<Timing Chart 2>
X100
X101
Y110
Final timing with no
execution of the last
JP instruction
3-84
Since the execution condition X101 for the differential
instruction has not changed from t he final timing with no
execution of the last JP instruction, no differential output is
obtained.
Since the execution condition X101 for the differential
instruction has changed from OFF to ON from the final timing
with no execution of the last JP instruction, differential output is
obtained.
JP 1
Y110
LBL 1
WUME-FP7CPUPGR-12

Advertisement

Table of Contents
loading

Table of Contents