Panasonic FP7 Series Command Reference Manual page 835

Cpu unit
Hide thumbs Also See for FP7 Series:
Table of Contents

Advertisement

● The case of SCU shows the case that it is used in the following combination.
• COM.0 port equipped in the CPU unit
• Communication cassettes attached to the CPU unit (COM.1 to COM.2 ports)
• Communication cassettes attached to the serial communication unit (COM.1 to COM.4
ports)
● The communication cassette (Ethernet type) does not support MODBUS.
I/O allocation (in the case of CPU with built-in SCU)
COM Port No.
1
2
0
XC
XD
XE
YC
YD
YE
Y0
Y1
Y2
(Note 1)
Each contact is used for reading the operation state. Do not write over it with a user program.
I/O allocation (in the case of Serial Communication Unit)
COM Port No.
1
2
3
XC
XD
XE
YC
YD
YE
Y0
Y1
Y2
(Note 1)
Each contact is used for reading the operation state. Do not write over it with a user program.
Precautions during programming (in the case of SCU)
● Use the UNITSEL instruction immediately before the SEND/RECV instruction to specify a
target port for communication.
● Master communication is only enabled when MEWTOCOL or MODBUS is selected. Confirm
that the "master communication clear to send flags" (XC to XF) are ON for the corresponding
channel, and execute the SEND/RECV instruction.
● Another SEND/RECV instruction cannot be executed for a communication port where master
communication is in progress. Confirm that the "master communication sending flags" (YC to
YF) are OFF, and execute the instruction.
WUME-FP7CPUPGR-12
15.6 SEND (MODBUS Master: Function Code Specification)
Name
Master
communication
clear to send flag
Master
communication
sending flag
Sent flag
Name
4
Master
XF
communication
clear to send flag
Master
YF
communication
sending flag
Y3
Sent flag
Turns ON when MEWTOCOL-COM, MEWTOCOL7, or MODBUS-
RTU is set for the communication mode, and the unit is in the
RUN mode.
Turns ON during sending data based on SEND/RECV instruction.
Turns OFF when the sending process is completed.
Reports completion result of sending data in genera-purpose
communication or master communication.
(Normal completion: 0, Abnormal completion: 1)
Turns ON when MEWTOCOL-COM, MEWTOCOL7, or
MODBUS-RTU is set for the communication mode, and the unit
is in the RUN mode.
Turns ON during sending data based on SEND/RECV
instruction.
Turns OFF when the sending process is completed.
Reports completion result of sending data in genera-purpose
communication or master communication.
(Normal completion: 0, Abnormal completion: 1)
Description
Description
15-41